products
  • NFC 33209 Aerial Bundle Cable

NFC 33209 Aerial Bundle Cable

Mainly used for 600V overhead secondary distribution lines.

We're here to help:Easy ways to get the answers you need.

  • Description
  • Parameter
Application:
Mainly used for 600V overhead secondary distribution lines. 
Standards: NFC 33-209; 

Using Characteristic:
1.The long-term allowable working temperature of cable conductor should not exceed 90℃;
2.The laying temperature of the cable shall be no less than -20 °C;

Construction:
1.Phase conductor: Aluminum conductor 
2.Neutral conductor: Aluminum alloy conductor
3.Public lighting: Aluminum conductor
4.Testing conductor: Copper conductor
5.Insulation: XLPE







 
ABC AAC/XLPE
Nominal cross sectional area Number of wires Insulation thickness Approximate outer diameter Approx.
weight 
Max. DC Resistance at 20℃
mm2 No. mm mm kg/km Ω/km
2x16 7 1.2 14.4 133 1.91
2x25 7 1.4 17.6 200 1.20
2x35 7 1.6 20.4 279 0.868
2x50 7 1.6 22.6 357 0.641
4x16 7 1.2 17.4 266 1.91
4x25 7 1.4 21.3 400 1.20
4x35 7 1.6 24.7 558 0.868
4x50 7 1.6 27.3 714 0.641
4x70 19 1.8 32.4 997 0.443

ABC AAC/XLPE+AAAC/XLPE
Nominal cross 
sectional area
Number
 of wires
Insulation 
thickness(mm)
Approximate outer diameter Approx.
weight 
Max. DC Resistance
 at 20 Ω/km
mm2 Phase 
Conductor
Neutral 
Conudctor
Phase 
Conductor
Neutral
 Conudctor
mm kg/km Phase
 Conductor
Neutral
 Conudctor
1x25+1x54.6  7 7 1.4 1.6 21.3  311.1 1.20 0.63
1x35+1x54.6  7 7 1.6 1.6 22.7  350.6 0.868 0.63
1x50+1x54.6  7 7 1.6 1.6 23.8  389.5 0.641 0.63
1x70+1x54.6  19 7 1.8 1.6 25.9  460.3 0.443 0.63
1x70+1x70 19 7 1.8 1.6 26.7  495.3 0.443 0.50
1x95+1x70 19 7 1.8 1.6 28.5  575.8 0.320 0.50
1x120+1x70 19 7 1.8 1.6 29.7  648.7 0.253 0.50
1x120+1x95 19 19 1.8 1.6 31.9  743.6 0.253 0.343
1x150+1x95 19 19 1.8 1.6 33.6  825.2 0.206 0.343
3x25+1x54.6  7 7 1.4 1.6 23.5  511.1 1.20 0.63
3x35+1x54.6  7 7 1.6 1.6 26.1  629.8 0.868 0.63
3x50+1x54.6  7 7 1.6 1.6 28.1  746.5 0.641 0.63
3x70+1x54.6  19 7 1.8 1.6 31.9  958.9 0.443 0.63
3x70+1x70 19 7 1.8 1.6 32.4  993.9 0.443 0.50
3x95+1x70 19 7 1.8 1.6 35.6  1235.4 0.320 0.50
3x120+1x70 19 7 1.8 1.6 37.8  1454 0.253 0.50
3x120+1x95 19 19 1.8 1.6 39.1  1548.9 0.253 0.343
3x150+1x95 19 19 1.8 1.6 42.2  1793.6 0.206 0.343
Nominal cross 
sectional area
Number
 of wires
Insulation
 thickness(mm)
Approximate 
outer 
diameter
Approx.
weight 
Max. DC 
Resistance
 at 20 Ω/km
mm2 Phase
 Conductor
Neutral
 Conudctor
Lighting
 Conductor
Phase
 Conductor
Neutral 
Conudctor
Lighting
 Conductor
mm kg/km Phase 
Conductor
Neutral 
Conudctor
Lighting 
Conductor
3x25+1x54.6+1x16 7 7 7 1.4 1.6 1.2 30.1 576 1.2 0.63 1.91
3x35+1x54.6+1x16 7 7 7 1.6 1.6 1.2 32.9 694 0.868 0.63 1.91
3x50+1x54.6+1x16 7 7 7 1.6 1.6 1.2 35.1 811 0.641 0.63 1.91
3x70+1x54.6+1x16 19 7 7 1.8 1.6 1.2 39.3 1023 0.443 0.63 1.91
3x70+1x54.6+1x25 19 7 7 1.8 1.6 1.4 39.3 1057 0.443 0.63 1.2
3x70+1x70+1x16 19 7 7 1.8 1.6 1.2 40.1 1058 0.443 0.50 1.91
3x95+1x70+1x16 19 7 7 1.8 1.6 1.2 43.7 1299 0.320 0.50 1.91
3x120+1x70+1x16 19 7 7 1.8 1.6 1.2 46.1 1518 0.253 0.50 1.91
3x120+1x95+1x16 19 19 7 1.8 1.6 1.2 48.3 1612 0.253 0.343 1.91
3x150+1x95+1x16 19 19 7 1.8 1.6 1.2 51.7 1857 0.206 0.343 1.91
3x25+1x54.6+2x16 7 7 7 1.4 1.6 1.2 30.1 642 1.2 0.63 1.91
3x35+1x54.6+2x16 7 7 7 1.6 1.6 1.2 32.9 761 0.868 0.63 1.91
3x50+1x54.6+2x16 7 7 7 1.6 1.6 1.2 35.1 877 0.641 0.63 1.91
3x70+1x54.6+2x16 19 7 7 1.8 1.6 1.2 39.3 1090 0.443 0.63 1.91
3x70+1x54.6+2x25 19 7 7 1.8 1.6 1.4 39.3 1157 0.443 0.63 1.2
3x70+1x70+2x16 19 7 7 1.8 1.6 1.2 40.1 1124 0.443 0.50 1.91
3x95+1x70+2x16 19 7 7 1.8 1.6 1.2 43.7 1366 0.320 0.50 1.91
3x120+1x70+2x16 19 7 7 1.8 1.6 1.2 46.1 1585 0.253 0.50 1.91
3x120+1x95+2x16 19 19 7 1.8 1.6 1.2 48.3 1678 0.253 0.343 1.91
3x150+1x95+2x16 19 19 7 1.8 1.6 1.2 51.7 1923 0.206 0.343 1.91

*Describe Your Buying Requirements in Detail