products
  • 0.6/1kV Copper conductor XLPE Insulated Steel tape armoured PVC Sheathed Control Cable(N2XBY)
  • 0.6/1kV Copper conductor XLPE Insulated Steel tape armoured PVC Sheathed Control Cable(N2XBY)

0.6/1kV CU/XLPE/STA/PVC Control Cable(N2XBY)

Copper conductor XLPE Insulated Steel tape armoured PVC Sheathed; Standard: IEC60502,IEC 60228 or other standard can customized.

We're here to help:Easy ways to get the answers you need.

  • Description
  • Parameter

Application:

The control cable is used as the connecting line between all kinds of electrical appliances, meters and automatic devices. It is mainly used for AC rated voltage 600/1000V and under control, monitoring circuit and protection circuit.

Construction 

1)Conductor : Copper ,Class 1 or Class 2,solid or stranded Circular conductors  

2)Insulation: Cross-linked polyethylene XLPE

3)Filler: Non-hygroscopic material

4)Binder tape: Non-hygroscopic material

5)Inner covering: Polyvinyl chloride PVC

6)Armour: Steel tape armour

7)Oversheath: Polyvinyl chloride PVC

 

 

Standard:

IEC 60228 Conductors of insulate cables

IEC 60502-1 Power cables with extruded insulation and their accessories for rated voltages from 1 kV(Um=1.2kV) up to 30kV(Um=36kV) - Part 1:Cables for rated voltages of 1 kV (Um=1.2kV) and 3 kV (Um=3.6kV)

No. of cores and nominal cross section

Thickness of Insulation

Thickness of Steel tape

Thickness of

 Sheath

Approx.

overall Diameter

Approx. weight

Max. DC resistance of conductor20

(mm2)

(mm)

(mm)

(mm)

(mm)

(kg/km)

(Ω/km)

KYJV22 (N2XBY) - 0.6/1kV

2X1.5

0.7

0.2

1.8

12.5

224

12.1

3X1.5

0.7

0.2

1.8

12.9

250

12.1

4X1.5

0.7

0.2

1.8

13.6

283

12.1

5X1.5

0.7

0.2

1.8

14.4

318

12.1

7X1.5

0.7

0.2

1.8

15.2

368

12.1

10X1.5

0.7

0.2

1.8

18

483

12.1

12X1.5

0.7

0.2

1.8

18.4

526

12.1

14X1.5

0.7

0.2

1.8

19.2

577

12.1

16X1.5

0.7

0.2

1.8

20

630

12.1

19X1.5

0.7

0.2

1.8

20.8

698

12.1

24X1.5

0.7

0.2

1.8

23.6

848

12.1

27X1.5

0.7

0.2

1.8

24

910

12.1

30X1.5

0.7

0.2

1.8

24.7

979

12.1

37X1.5

0.7

0.2

1.8

26.4

1135

12.1

44X1.5

0.7

0.2

1.9

29.3

1334

12.1

48X1.5

0.7

0.2

1.9

29.8

1409

12.1

52X1.5

0.7

0.2

1.9

30.5

1495

12.1

61X1.5

0.7

0.2

2.0

32.7

1736

12.1

2X2.5

0.7

0.2

1.8

13.3

262

7.41

3X2.5

0.7

0.2

1.8

13.8

298

7.41

4X2.5

0.7

0.2

1.8

14.6

344

7.41

5X2.5

0.7

0.2

1.8

15.5

392

7.41

7X2.5

0.7

0.2

1.8

16.4

463

7.41

10X2.5

0.7

0.2

1.8

19.6

616

7.41

12X2.5

0.7

0.2

1.8

20.1

680

7.41

14X2.5

0.7

0.2

1.8

21

754

7.41

16X2.5

0.7

0.2

1.8

21.8

829

7.41

19X2.5

0.7

0.2

1.8

22.8

928

7.41

24X2.5

0.7

0.2

1.8

26

1136

7.41

27X2.5

0.7

0.2

1.8

26.5

1228

7.41

30X2.5

0.7

0.2

1.8

27.3

1329

7.41

37X2.5

0.7

0.2

1.9

29.4

1573

7.41

No. of cores and nominal cross section

Thickness of Insulation

Thickness of Steel tape

Thickness of

 Sheath

Approx.

overall Diameter

Approx. weight

Max. DC resistance of conductor20

(mm2)

(mm)

(mm)

(mm)

(mm)

(kg/km)

(Ω/km)

KYJV22 (N2XBY) - 0.6/1kV

44X2.5

0.7

0.2

2.0

33.1

1884

7.41

48X2.5

0.7

0.2

2.0

33.6

2000

7.41

52X2.5

0.7

0.2

2.0

34.4

2128

7.41

61X2.5

0.7

0.2

2.1

36.5

2435

7.41

2X4

0.7

0.2

1.8

14.2

313

4.61

3X4

0.7

0.2

1.8

14.8

365

4.61

4X4

0.7

0.2

1.8

15.7

427

4.61

5X4

0.7

0.2

1.8

16.8

493

4.61

7X4

0.7

0.2

1.8

17.8

595

4.61

10X4

0.7

0.2

1.8

21.5

803

4.61

12X4

0.7

0.2

1.8

22.1

897

4.61

14X4

0.7

0.2

1.8

23

1002

4.61

16X4

0.7

0.2

1.8

24.1

1110

4.61

19X4

0.7

0.2

1.8

25.1

1255

4.61

24X4

0.7

0.2

1.9

29.4

1587

4.61

27X4

0.7

0.2

1.9

30

1725

4.61

30X4

0.7

0.2

1.9

30.9

1873

4.61

37X4

0.7

0.2

2.0

33.2

2228

4.61

44X4

0.7

0.5

2.2

38.5

3007

4.61

48X4

0.7

0.5

2.2

39.1

3187

4.61

52X4

0.7

0.5

2.2

40.4

3428

4.61

61X4

0.7

0.5

2.3

42.7

3900

4.61

*Describe Your Buying Requirements in Detail